Prime Power |
||
| Prime | kVA | 308 |
| Prime | kW | 246,4 |
| Current | (cos Phi=0,8) A | 443,52 |
| Standart Voltage | V | 230/400 |
| Revolution Per Minute | r.p.m | 1500 |
| Rated At Power Factor | Cos Phi | 0,8 |
Standby |
||
| Standby | kVA | 280 |
| Standby | kW | 224 |
| Current | (cos Phi=0,8) A | 403,2 |
| Standart Voltage | V | 230/400 |
| Revolution Per Minute | r.p.m | 1500 |
| Rated At Power Factor | Cos Phi | 0,8 |
| Brand | LISTER PETTER | |
| Model | LP612G1 | |
| Model Series | Venüs | |
| Emission | Stage II | |
| Fuel Type | 4 Stroke – Diesel | |
| Injection Type and System | Indirect injection | |
| Aspiration | Turbo Charge & Air-Air Intercooler | |
| Governor System | Elektronic | |
| Number of Cylinders | 6 | |
| Bore and Stroke | mmxmm | 128×153 mm |
| Total Displacement | lt | 11,8 |
| Cooling System | Water Cooled | |
| Compression Ratio | 17:01 | |
| Fuel Consumption 50% PRP | lt/s | 30,3 |
| Fuel Consumption 75% PRP | lt/s | 47,5 |
| Fuel Consumption 100 % PRP | lt/s | 58,8 |
| Fuel Consumption Standby | lt/s | 65,5 |
| Total oil capacity | lt | 41 |
| Total coolant capacity | lt | 56 |
| Alternator | ||
| No of Phases | 3 | |
| Power Factor | 0,8 | |
| No of Bearings | Single | |
| No of Poles | 4 | |
| No of Leads | 6-12 | |
| Insulation Class | H | |
| Degree of Protection | IP23 | |
| Excitation System | AVR |
Dimensions Without Canopy and Weight |
||
| Witdh | mm | 2980 |
| Length | mm | 1250 |
| Height | mm | 2100 |
| Weight | kg | 2500 |
| Fuel Tank Capacity | lt | 590 |
Dimensions With Canopy and Weight |
||
| Witdh | mm | 3950 |
| Length | mm | 1250 |
| Height | mm | 2450 |
| Weight | kg | 2900 |